Date: 2022-06-10
Document version: 1.5
Valid for: MiR100 and MiR200
Valid for software version: All
Valid for hardware version: All
This article describes how to apply the factory default configuration to the SICK safety system used in MiR100 and MiR200.
A PC with the SICK Flexi Soft Designer application. This can be downloaded from SICK’s website.
The correct project file for your robot. Below you will find a list of MiR hardware versions and their corresponding SICK configuration files. It is important that the correct file is used, or the robot will be locked in Protective stop until the correct file is applied.
| Original name | HW version | Configuration file | Flexi Soft Designer version |
|---|---|---|---|
| R0000 – R0353 | 1.0–1.8 | MiR100-HW 1.0-1.8 | 1.9.2 Sp1 |
| R0354–R0599 | 1.9 | MiR100-HW 1.9 | 1.9.2 Sp1 |
| R0600–R1080 | 2.0–2.2 | MiR100-HW 2.0-2.1-2.2 | 1.9.2 Sp1 |
| R1081–R1335 | 3.0 | MiR100-HW 3.0 | 1.9.2 Sp1 |
| R1336–R1499 | 4.0 | MiR100-HW 4.0 | 1.9.2 Sp1 |
R1530 and higher or | 5.0 | MiR100-HW 5.0 | 1.9.2 Sp1 |
| MiR_201704000 and higher | 6.0–7.0 | MiR100-HW 6.0-7.0 | 1.9.2 Sp1 |
| Original name | HW version | Configuration file | Flexisoft Designer version |
|---|---|---|---|
| S0001–S0178 | 1.0 | MiR100-HW 1.0 | 1.9.2 Sp1 |
| S0179–S0607 | 1.1–1.3 | MiR100-HW 1.1-1.2-1.3 | 1.9.2 Sp1 |
| S0608–S0905 | 2.0 | MiR100-HW 2.0 | 1.9.2 Sp1 |
| S0906–S1109 | 3.0 | MiR100-HW 3.0 (version described in SICK configuration file release note) | 1.9.2 Sp1 |
S1110 and higher | 5.0 | MiR100-HW 5.0 (version described in SICK configuration file release note) | 1.9.2 Sp1 |
| MiR_201905000 and higher | 6.0 | MiR200-HW 6.0 | 1.9.2 Sp1 |
If you apply the wrong file, the robot will enter Protective stop. You can release it by applying the correct file version
Find your robot’s hardware version on the identification label on the robot or in the Declaration of Conformity you received when you purchased the robot.



Choose your wireless network adapter from the drop-down menu. This must be the network used to connect to the robot.
Enter the IP address: 192.168.12.9
Enter the TCP/IP configuration port: 9000
Check Enable TCP/IP routing
Enter Subnet Address: 255.255.255.0
Select OK to save the profile.


If you see a green check mark next to the small connector icon, proceed to the next step.
If you see a red or white X, select Edit Connection and make sure you chose the correct network adapter.
If you are offline or the network is not appearing in the drop-down menu, connect an Ethernet cable to the top of the robot.
If you are still having trouble connecting to the robot:
Right click the network icon in the system tray.
Select Open network settings.
Select Wifi in the sidebar and scroll down to Change adapter options.
Right click the WiFi adapter, and go to properties.
Uncheck Internet Protocol Version 6 (TCP/IPv6) and select OK.






Flexi Soft designer will create a safety report for each device configured that shows the changes that have been made to the safety zones.



It is important to perform a test to ensure the zones are switching correctly. To do this, power on the robot and test the safety features:
Emergency stop. Test the Emergency stop button by pressing and releasing it. The robot’s status lights should turn red when the button is pressed.
Protective stop. Test the scanner safety zones by placing an object in front of the scanners and making sure the robot enters Protective stop (the status lights turns red).
| Version | Date | Description |
|---|---|---|
| 1.5 | 2022-06-10 | Added SICK configuration files for HW 6.0 and 7.0. |
| 1.4 | 2021-05-03 | Improvements throughout the guide. |
| 1.3 | 2021-04-23 | Added robots with 9-digit serial numbers to the overview table. |
| 1.2 | 2020-09-02 | Updated SICK password information. Small corrections throughout the guide. |
| 1.0-1.1 | 2020-06-15 | Undocumented changes. |